Appendix D

Technical Data of UHV DC Transmission Lines

Table D.1

Technical Data of UHV DC Transmission Lines.

Technical Data Xiangjiaba–Shanghai ±800 kV UHV DC Transmission Line
Rated operating voltage (kV) ±800
Maximum operating voltage (kV) ±816
Transmission capacity (MW) 6400
Rated current (A) 4000
Minimum clearance Under switching overvoltage for common lines At an altitude of 500 m: 5.5 m
At an altitude of 1000 m: 5.7 m
At an altitude of 2000 m: 6.2 m
Under operating voltage for common lines At an altitude of 500 m: 2.1 m
At an altitude of 1000 m: 2.3 m
At an altitude of 2000 m: 2.5 m
For large-crossing lines 6.1 m under switching overvoltage
2.55 m under operating voltage
Minimum height of conductor above ground (m, ...