Using RLUs to Determine In-Feed Capacities

In-feed capacities are the grand totals of the power, cooling, physical space, weight, and bandwidth you will need to support a given number of racks. Let's say you plan to build a data center with 40 Sun Fire 6800 servers (RLU-C). Each Sun Fire 6800 server will have four Sun StorEdge racks (RLU Superset-A) connected to it. That's 40 RLU-Cs and 160 RLU Superset-As.

The following table shows the total floor load support and in-feed requirements for these RLUs.

Table 4-3. Total In-Feeds for Racks
Specifications 40 RLU-C Racks 160 RLU Superset-A Racks Totals
Weight 40,000 lbs (18,144 kg) 155,200 lbs (70,398 kg) 195,200 lbs (88,542 kg)
Power 160 30Amp 208V L6-30R outlets

RM=2

339,506 W × RM = 679,012 W

Get Enterprise Data Center Design and Methodology now with the O’Reilly learning platform.

O’Reilly members experience books, live events, courses curated by job role, and more from O’Reilly and nearly 200 top publishers.